Scolmore Sites

Click Litehouse

Click Litehouse

Visit the site...

Ovia Australia

OVIA Australia

Visit the site...

Click Smart

Clicksmart

Visit the site...

Scolmore group

Scolmore Group

Visit the site...

Scolmore Dubai

Scolmore Dubai

Visit the site...
  • MAGDUO4

    4 Zone Two Wire Fire Panel

    • Two Wire fire alarm system
    • Active end of line monitoring and head removal
    • Up to 32 devices per zone (Dependent on Device Loading Unit: DLU)
    • 4 line x 20 character LCD display
    • Ability to differentiate between smoke detector, heat detector or a manual call point alarms
    • Alarm confirmation feature
    • RS485 connection to up to 8 repeater panels
    • Event log storing up to 500 events
    • 3 enhanced test modes
    • Zone can be configured to day/night detection mode
    • Delay programming options
    • 4 or 8 zone panel can now be configured to accept conventional devices on zones 5 to 8 with the optional conventional zone card
    • Certified to EN54 2/4 Standards
    • Requires 2 x 12V 2.3Ah batteries (BAT32)
    • Optional extended battery box with capacity for 2 x 12V 7.0Ah batteries

Technical Specifications

Inputs
Max Detectors Per ZoneUp to 32 Devices (Dependant on Device Loading Units , 160 per Zone)
Power
Mains Supply 230VAC, +10%, -15%, 50/60Hz
Operating Voltage 24vDC (Range 21-31vDC)
Standby Supply2 x 12V 3.2Ah S.L.A Battery
Outputs
Zone Up to 4 (300mA)
Monitored Sounder CircuitsUp to 2 (250 mA)
Monitored Relay CircuitsUp to 2 (250 mA)
Auxiliary Output24vDC (300mA)
Environment
Working Temperature5°C to 40°C
Dimensions 333 x 333 x 99mm
Weight 2.28 Kg